Specifications
- Measuring ranges
- Earth resistance: 0-12Ω / 0-120Ω / 0-1200Ω
- Earth voltage: 0-30 Vac (40-500Hz)
- Accuracy
- Earth resistance: ±3% of full scale
- Earth voltage: ±2.5% of full scale
- Measuring system: Earth resistance by constant current inverter 820 Hz, 2mA approx.
- Open circuit: indication LED will be unlit
General
- Dimensions: 175(L) × 85(W) × 75(D)mm.
- Weight (battery included): Approx. 600g.
- Power source: 1.5V (AA) × 8.
- Safety Standard: EN 61010-1 CAT IV 30V. EN 61326-1.
Accessories: Instruction manual. Test leads (red-15m, yellow -10m, green-5m). Auxiliary earth spikes. Simplified measurement probe. Shoulder belt. Battery.