Specifications
- Measuring ranges
- Earth resistance: 0-20Ω / 0-200Ω / 0-2000Ω
- Earth voltage: 0~200V (40~500Hz)
- Accuracy
- Earth resistance: ±(2%rdg+2dgt) at 200/2000Ω. ±(2%rdg+0.1Ω) at 20Ω
- Earth voltage: ±(1%rdg+2dgt)
- Earth resistance resolution
- 0-20Ω : 0.01Ω
- 0-200Ω : 0.1Ω
- 0-2kΩ : 1Ω
- Measuring system: Earth resistance by constant current inverter 820 Hz, 2mA approx.
- Open circuit indication: LED will be unlit
General
- Display: 3½ digit (2000 counts).
- Low battery indication.
- Data hold indication.
- Over range indication: “1”(MSD).
- Dimensions: 250(L) × 190(W) × 110(D)mm.
- Weight (battery included): Approx. 1500g.
- Power source: 1.5V (AA) × 8.
- Safety Standard: EN 61010-1 CAT III 300V. IEC 61557-1. IEC 61557-5. EN 61326-1.
Accessories: Instruction manual. Test leads (red-15m, yellow -10m, green-5m). Auxiliary earth spikes. Simplified measurement probe. Shoulder belt. Batteries.