Specifications
- Measuring ranges
- Earth resistance: 0-20Ω / 0-200Ω / 0-2kΩ
- Earth voltage: 0~300V AC
- Earth Resistivity: 0.06~6.28kΩ.m / 0.62~62.8kΩ.m / 6.28~628kΩ.m
- Accuracy
- Earth resistance: 0-20Ω: ±(2%rdg+0.1Ω)
- Earth resistance: 0-200Ω,0-2kΩ: ±(2%rdg+3dgt)
- Earth voltage: ±(2%rdg+3dgt)
- Earth resistance resolution
- 0-20Ω : 0.01Ω
- 0-200Ω : 0.1Ω
- 0-2kΩ : 1Ω
- Measuring system: Earth resistance by constant current inverter 820 Hz, 2mA approx.
General
- Operating temp. & humidity: 0°C~40°C ≤80% R.H.
- Storage temp. & humidity: -10°C~50°C ≤80% R.H.
- Dimensions: 250(L) x 190(W) x 110(D)mm.
- Weight (battery included): Approx. 1500g.
- Power source: 1.5V (AA) × 8.
- Safety Standard: EN 61010-1 CAT IV 300V. EN 61326-1. EN 61557-1. EN 61557-5.
Accessories: Instruction manual. Test leads (red-15m, yellow -10m, green-5m). Auxiliary earth spikes. Carry case. Shoulder belt. Batteries. Data Transmission cable CA-232(4236ER). Compact disc(CD) for PC interface(4236ER).