Specifications
● Test voltage: from 500Vdc to 10kVdc adjustable in 500V steps
● Preset buttons: 1kV, 2.5kV, 5kV, 10kV
● Measuring ranges (Auto-Ranges): 800kΩ-500GΩ (auto-ranging)
● Accuracy: ± 5% ± 2 digits
● Output power limit: 1W
● Voltage regulation: Selected voltage +20%-5% of nominal value unless current limited. Meaning that if output current is too high, the voltage will be lowered automatically.
● Operating temp.: 0°C to 40°C, R.H. 85% Max.
● Dimensions: 330(L) × 260(W) × 160(D) mm
● Weight (battery included): Approx. 3600g
● Power source: 1.5V “C”× 8 Alkaline batteries.
● Safety Standard: EN 61010-1 CAT III 600V. EN 61326-1.
Accessories: Instruction manual, Color coded flexible silicone test leads, Batteries.