6213A IN Digital HV Insulation Tester (0.5kV-10kV)

SKU:
6213AIN
$2,158.00
  • Microprocessor-controlled.
  • 2 ×16 characters; large intelligent LCD module.
  • 20 Insulation test voltages from 0.5kV to 10kV (0.5kV increment steps).
  • Ener-Save™ feature to extend battery life.
  • Bargraph indicates test voltage; rise and decay can be observed.
  • Visual and audible warning if external voltage is present(>500Vac or Vdc.)
  • Insulation resistance; auto-ranging on all ranges.
  • Overload protection.
  • Low battery indicator (read time battery voltage measurement).
  • Measures insulation time duration of the test.
  • Low battery consumption.
  • Better than 10% accuracy on all ranges.
  • Auto-off.
  • Calculates Dielectric Absorption Ratio (DAR) automatically.
  • Calculates Polarization Index (PI) automatically.
$2,158.00

Specifications

  • Test voltage (DC V): 20 Insulation test voltages from 500Vdc to 10kVdc adjustable in 500V steps
  • Preset buttons: 1kV / 2.5kV / 5kV / 10kV
  • Measuring ranges (Auto-Ranges): 800kΩ-500GΩ (auto-ranging)
  • Accuracy: ± 5% ± 2 digits
  • Output power limit: 1W
  • Voltage regulation: Selected voltage +20%-5% of nominal value unless current limited. Meaning that if output current is too high, the voltage will be lowered automatically.

General

  • Operating temperature: 0°C to 40°C
  • Operating humidity: 85% Max. relative humidity
  • Dimensions: 330(L) × 260(W) × 160(D) mm
  • Weight (battery included): Approx. 3600g
  • Power source: 1.5V “C”× 8 Alkaline batteries
  • Safety Standard: EN 61010-1 CAT III 600V. EN 61326-1

Accessories: Instruction manual, Color coded flexible silicone test leads, Batteries.