Specifications
RCD Testing
- Range: 10mA @ 150ms / 30mA @ 150ms / 150mA @ 30ms
- Accuracy: ± 10%
LOOP Testing
- Range: Supply Loop / Supply Loop +1Ω
- Accuracy: 0.45Ω ± 0.05Ω / 1.45Ω ± 0.05Ω
Continuity Testing
- Range: 0.5Ω / 2Ω / 10Ω
- Accuracy: ± 0.05Ω / ± 0.1Ω / ± 0.2Ω
- Max. Current: 300mA
Insulation Testing
- Range: 1MΩ / 9.9MΩ / 99MΩ
- Accuracy: ± 1%
- Max. Testing: 1.2kV
General
- Dimension: 330(L)x260(W)x160(D)mm.
- Weight: Approx. 2570g.
- Safety standard: EN 61010-1 / EN 61326-1