Specifications
- Test voltage (DC V): 1000V / 2500V / 5000V / 10000V
- Insulation resistance:
- 2TΩ / 1000V
- 5TΩ / 2500V
- 10TΩ / 5000V
- 20TΩ / 10000V
- Accuracy:
- 0~200GΩ / 1000V: ±(5.0%rdg + 5dgt)
- 0~500GΩ / 2500V: ±(5.0%rdg + 5dgt)
- 0~1000GΩ / 5000V: ±(5.0%rdg + 5dgt)
- 0~2000GΩ / 10000V: ±(5.0%rdg + 5dgt)
- 200G~2TΩ / 1000V: ±20%rdg
- 500G~5TΩ / 2500V: ±20%rdg
- 1000G~10TΩ / 5000V: ±20%rdg
- 2000G~20TΩ / 10000V: ±20%rdg
- Resolution:
- 1000MΩ: 1MΩ
- 10GΩ: 0.01GΩ
- 100GΩ: 0.1GΩ
- 1TΩ: 1GΩ
- 10TΩ: 10GΩ
- 20TΩ: 100GΩ
- Short circuit current: up to 5mA
- Current measurement: 0.5nA ~ 0.55mA (Depending on the insulation resistance)
Voltmeter
- ACV: 30~600V (50/60Hz)
- DCV: 30~600V
- Accuracy: ±(2.0%rdg + 3dgt)
- Resolution: 1V
General
- Dimensions: 330(L) × 260(W) × 160(D)mm
- Weight (battery included): Approx. 4724g
- Power source: 1.5V "C" × 8 Alkaline batteries
- Safety Standard: EN 61010-1 CAT IV 600V. EN 61010-2-030. EN 61326-1.
Accessories: Instruction manual, Test leads, Data transmission cable CA-232, Compact disk (CD) for PC interface, Alligator clips, Batteries, Test report.