Specifications
- Withstand voltage (On insulating rod): 100kV / 300mm: 1 minutes.
- Insulation resistance: 2000MΩ min by 1kV / DC megger at the same testing location as withstand voltage.
- Leakage current: 100uA or less than 100uA at withstand voltage test.
- Measuring voltage range: 6kV~81.5kV.
- Operation start voltage (To ground): 2.7kV.
- Display Light: Flashing red light.
- Sound: Intermittent sound 50 dB apart 3 m.
- Frequency: 50/60Hz.
General
- Operating temperature: 0°C ~ 40°C.
- Battery: 2 button-cells LR44(1.5V).
- Overall length:
- Retracted 1370±50mm,
- Extracted 2450±50mm.
- Weight (battery included): Approx. 590g.
- Safety standards: IEC / EN 61243-1.
Accessories: Instruction manual, Soft pouch.