1832 IN Analog Insulation Tester (250V, 500V, 1000V)

SKU:
1832IN
$470.00
  • High quality Taut Band movement.
  • Three insulation test voltages(DC): 250V, 500V, 1000V.
  • Two continuity test on low ohms 3Ω & 500Ω.
  • Compact and lightweight.
  • 200mA continuity short circuit current.
  • 1mA test current on insulation test at nominal voltage.
  • Automatic discharge of capacitive and inductive circuit with charge stored in the circuit under test.
  • Live warning and display or external voltage presence.
  • Fuse, air gap, crowbar and overload protected.
  • On line battery monitoring shows if battery is ok.
  • Manual zero ohm adjustment.
  • Low battery consumption.
  • Mirror scale.
  • Push and turn locking switch for continuous and hand free testing.
  • BS 16 edition.
$470.00

Specifications

Insulation Resistance

  • Test voltage (DC V): 250V / 500V / 1000V
  • Output voltage on open circuit: Rated test voltage +10%
  • Measuring ranges: 0-100MΩ / 0-200MΩ / 0-400MΩ
  • Mid-scale value: 1MΩ / 2MΩ / 4MΩ
  • Scale multiplier: ×1/2 / ×1 / ×2
  • Accuracy: ± 3% of indicated value
  • Output short- circuit current: ≥ 1.0mA

Continuity

  • Measuring ranges: 3Ω / 500Ω
  • Accuracy: ± 1.5% of scale length
  • Output short-circuit current: ≥ 200 mA

AC Voltage

  • Range: 0-600V AC
  • Accuracy: ± 3% of scale length

General

  • Voltage warning: Warning light circuit live lit From 90Vdc/70Vac. Buzzer beep from 24V ac/dc.
  • Battery check: Battery check indicate good batteries from 8Vdc to 13Vdc during a load test of 205mA.
  • Battery OK: Battery OK LED lit from 8Vdc and is operative while testing.
  • Dimensions: 170(L) × 165(W) × 92(D)mm.
  • Weight (battery included): Approx. 1030g.
  • Power source: 1.5V (AA) × 8.
  • Safety Standard: EN 61010-1 CAT III 600V. EN 61326-1.

Accessories: Instruction manual, Test leads, Batteries, Shoulder belt.