Specifications
- Test voltage: From 500Vdc to 15kVdc, adjustable in 500V steps
- Preset buttons: 1kV, 5kV, 10kV, 15kV
- Insulation resistance:
- 1TΩ / 0.5kV
- 1TΩ at 0.5kV ~ 30TΩ at 15kV
- Accuracy:
- 1kV: 0~200GΩ: ±(5.0%rdg + 5dgt)
- 5kV: 0~1TΩ: ±(5.0%rdg + 5dgt)
- 10kV: 0~2TΩ: ±(5.0%rdg + 5dgt)
- 15kV: 0~3TΩ: ±(5.0%rdg + 5dgt)
- 1kV: 200GΩ~2TΩ: ±20%
- 5kV: 1TΩ~10TΩ: ±20%
- 10kV: 2TΩ~20TΩ: ±20%
- 15kV: 3TΩ~30TΩ: ±20%
- Resolution:
- 1GΩ: 0.001GΩ
- 10GΩ: 0.01GΩ
- 100GΩ: 0.1GΩ
- 1TΩ: 1GΩ
- 10TΩ: 10GΩ
- 30TΩ: 100GΩ
- PI (Polarization Index)
- DAR (Dielectric Absorption Ratio)
- Short circuit current: up to 5mA
- Current measurement: 0.5nA ~ 0.55mA (Depending on the insulation resistance)
Voltmeter
- ACV: 30~600V (50/60Hz)
- DCV: 30~600V
- Accuracy: ±(2.0%rdg + 3dgt)
- Resolution: 1V
General
- Dimensions: 430(L) x 324(W) x 127(D)mm
- Weight (battery included): Approx. 6.56kg
- Power source: Rechargeable battery
- Adapter:
- Input: 100-240VAC, 0.4A, 50-60Hz
- Output: 24VDC, 0.62A
- Safety Standard: EN 61010-1 CAT IV 600V. EN 61010-2-030. EN 61326-1.
Accessories: Instruction manual, Test leads (AL-58HV, AL-30AG,AL-30HB), Data transmission cable CA-232, Compact disk (CD) for PC interface, Alligator clips (AL-23CA), Charger (CHA-7015), Test report.