Specifications
Display: 4 rows, 4 digits (Lowest 8 digits for energy display), LCD with Backlight.
Input
- Type of measurement: TRUE RMS.
- Sampling rate: 64 Samples / Cycle.
- Electrical connections: 3Ø - 3 wire (Delta), 3Ø - 4 wire (Wye), 2Ø - 3 wire, 1Ø - 2 wire (L-N).
- Data update rate: 1 sec.
- Input-voltage:
- PT primary: 100V to 500kV (Programmable for any value)
- PT secondary: 100V to 500V AC (L-L) (Programmable for any value)
- Voltage nominal: 240VAC L-N / 415V AC L-L. - Input current:
- CT ratings primary: 1 / 5A to 10kA (Programmable for any value)
- CT ratings secondary: 1 / 5A (Programmable for any value)
- Current nominal: 5A
Output
- Pulse output
- Voltage Range: External 24V DC max
- Current Capacity: 100mA max
- Pulse Width : 100ms ±5ms
- Configurable pulse weight from 1 to 9999000 pulses / kWh. - Device ID & Parity 1 to 255 & None, Odd, Even.
- Protocol & Interface RS485 and MODBUS RTU.
- Transmission mode Half duplex.
- Data types Float and Integer .
- Transmission distance 500m maximum.
- Transmission speed 1200, 2400, 4800, 9600,19200 (in bps).
- Stop bits 1 or 2.
- Response time 100ms (max and independent of baud rate).
- Isolation 2kV RMS.
General:
- Weight 318gms (11Oz)
- Material LEXAN 923-701 BLACK
- IP degree of protection (IEC 60529) IP54 Front only
- Torque at terminals 0.68N-m to 0.79 N-m
- Wire gauge at terminals 20 to 14AWG;75°C
- Mounting position Vertical
- Auxiliary Supply Specifications